0
Your shopping cart is empty!

Close

SIP380B20BD.9-33

Связь инжиниринг

Price: BY REQUEST!

Оnline UPS SIP380B20BD.9-33 double conversion with a three-phase input and output, with a total power of 20 kVA and with the connection of external battery cabinets. Transformer inverter for galvanic isolation. Output power factor 0,9. Parallel operation of up to four UPS. Compatible with generator sets and have high overload capacity.

Connection

  • Output power factor 0.9 provides active power up to 18 kW
  • System with three-phase output voltage and zero switchover time to batteries
  • Additional load protection - integrated inverter transformer provides galvanic isolation in linear mode
  • Power up or redundancy N + x by parallel connection of up to 4 devices
  • As part of a parallel system, it is possible to work with common or separate battery cabinets
  • Minimal load on the mains or generator due to the low input harmonic distortion coefficient
  • Input filter to reduce the impact on the mains
  • Output transformer for galvanic isolation of input and output

Control

  • Control interfaces: RS-232/485, slot for cards SNMP and dry contacts
  • Emergency power off (EPO)
  • Graphic LCD and LED mnemonic panel

Installation and operation

  • Compatible with generator sets
  • Wide range of input voltage and frequency
  • High overload capacity - up to 150%
  • High efficiency mode for energy saving (ECO mode)
  • Intelligent battery charging for extending battery life
  • Automatic self-test to increase system reliability
Product Code: 191-03
General
UPS model SIP380B20BD.9-33
Apparent Power, kVA 20
Active power, kW 18
Input phases 3 phases
Output phases 3 phases
Form factor Tower
Warranty 24 months
Input
Rated input voltage 380, 400, 415 V
Rated voltage range 380, 400, 415 V (- 25%...+ 20%)
Input frequency range 50/60 Hz ± 5 Hz
Rated input current 43 ampere
Input power factor over 0,9 (when using a filter)
Total harmonic distortion at the input Less than 10% when using a filter
Voltage range in ECO mode From - 40% up to + 20% (customizable)
Input connection type Connection terminal, three phases + neutral
Output
Rated output voltage 380, 400, 415 V
Output voltage accuracy ± 1 %
Topology and form of the output voltage Online UPS with pure sine wave output
Distortion of the output voltage ≤ 3% on linear load
Output frequency (battery mode) 50, 60 Hz ± 0.05%
Output power factor 0.9
Peak load ratio 3:1
Overload capacity When working from the mains: up to 110% - 30 minutes, up to 125% - 10 minutes, up to 150% - 1 minute
Efficiency in online mode 89%
Efficiency in ECO mode 98%
Surge Protection n/a
Filtering n/a
Type of output connection Connection terminal, three phases + neutral
Bypass circuit (bypass)
Bypass type Electronic and manual service bypass
Bypass voltage range From - 40% up to + 20%
Bypass frequency range ± 20%
Battery
Built-in battery None
Battery Type Leak-acid sealed with leakage protection
DC bus voltage 384 V direct current (DC)
Battery life (50% and 100% load) Depending on the capacity of the connected battery cabinet
Recharge time Depending on the capacity of the connected battery cabinet
Charge mode Intelligent charge with temperature compensation voltage
Charge current 46 ampere
Transfer time to batteries 0 ms - from the mains to the battery
Battery Protection Over discharge, overvoltage and short circuit protection
Communications and Interfaces
Interface ports RS232/485
Internal slot for control card SNMP card slot or dry contact
Emergency power off (EPO) Do have
LCD display and indication Digital LCD display and LED indication
Sound alarm Mains failure, low battery, overload, UPS error
Working Conditions
Operating temperature 0°C ~ 40°C
Operating relative humidity 0 ~ 95 %
Operating height above sea level 0 ~ 3000 meters - up to 85% load, 0 ~ 1500 meters - 100% load
Storage temperature - 25°C ~ + 55°C
Storage height above sea level 0 ~ 10000 meters (recommended)
Protection class IP20, optional other degrees of protection available
Heat dissipation in online mode 7590 BTU/hour
Noise level Less than 63 dB
Physical Characteristics
Unit size (W х D х H), mm 570x800x1195
Shipping Unit size (W х D х H), mm 668x908x1379
Net weight, kg 242
Shipping weight, kg 288
Compliance with standards
Safety TR TS 004/2011, IEC 62040-1
ЕМС TR TS 020/2011, IEC 62040-2


Official website of the company: © Parus Electro, 2011-2020

All information published on the website is for guidance only and under no circumstances is a public offer determined by the provisions of Article 437.

Uninterruptible power supply equipment: UPS (Uninterruptible Power Supply), Rechargeable batteries.

Яндекс.Метрика