0
Your shopping cart is empty!

Close

SIP380A15МDС.10-33

Связь инжиниринг

Price: BY REQUEST!

Power module SIP380A15МDС.10-33 for SIP380A MD series modular UPS with three-phase input and output a total power of 15 kVA. Occupies a 3U height in cabinet of a modular UPS. Able to install redundant N + x modules. LCD display and control buttons on front panel.

Connection

  • Output power factor of 1.0 provides an active power up to 15 kW
  • Double conversion system and zero switchover time to batteries
  • Possible parallel operation of several modular systems
  • Minimal load on the mains or generator due to the low input harmonic distortion coefficient

Control

  • UPS cabinet has RS-232/485 control interfaces, ModBus ports, SNMP card slots and dry contacts
  • Remote Emergency Power Off (REPO) in the UPS cabinet
  • General touchscreen LCD display for entire UPS system
  • Digital LCD display on each power module

Installation and operation

  • Execution in dimensions of 19" telecommunication racks for compact placement
  • Wide range of input voltage and frequency
  • High conversion efficiency of at least 95%
  • Possible Hot swapping of modules without shutdown
  • MTBF of up to 250 000 hours
  • High efficiency mode for energy saving (ECO mode)
  • Intelligent battery charging for extend of battery life
  • Automatic self-test to increase system reliability
Product Code: 577-20
General
Power module model SIP380A15MDS.10-33
Apparent Power, kVA 15
Active power, kW 15
Input phases 3 phases
Output phases 3 phases
Form factor Module 3U
Warranty 24 months
Input
Rated input voltage 380, 400, 415 V
Input connection type Bus connector for modular UPS cabinet
Output
Rated output voltage 380, 400, 415 V
Topology and form of the output voltage Online UPS with pure sine wave output
Filtering Integrated filter
Type of output connection Bus connector for modular UPS cabinet
Bypass circuit (bypass)
Bypass type Electronic, as part of the UPS cabinet manual maintenance bypass
Battery
DC bus voltage ± 192 V (optional ±204, 216, 228, 240 V) direct current (DC)
Charge current Up to 6 ampere
Transfer time to batteries 0 ms - from the mains to the battery
Communications and Interfaces
LCD display and indication LCD display and LED indicators
Sound alarm Mains failure, low battery, overload, UPS error
Working Conditions
Operating temperature 0°C ~ 40°C
Operating relative humidity 0 ~ 95 %
Operating height above sea level 0 ~ 3000 meters - up to 85% load, 0 ~ 1500 meters - 100% load
Storage temperature -25°C ~ +55°C
Storage height above sea level 0 ~ 10000 meters (recommended)
Physical Characteristics
Unit size (W х D х H), mm 443x580x131
Shipping Unit size (W х D х H), mm 575x710x231
Net weight, kg 30
Shipping weight, kg n/a
Compliance with standards
Safety TR TS 004/2011, IEC 62040-1, IEC 60950-1
ЕМС TR TS 020/2011, IEC 62040-2, IEC 61000-4-2/61000-4-3/61000-4-4/61000-4-5/61000-4-6/61000-4-8


Official website of the company: © Parus Electro, 2011-2020

All information published on the website is for guidance only and under no circumstances is a public offer determined by the provisions of Article 437.

Uninterruptible power supply equipment: UPS (Uninterruptible Power Supply), Rechargeable batteries.